ELRM44V-30 Type A Earth Leakage Relay

  • Type A – Earth Leakage Relay
  • Selectable Trip level (0.03 – 30A) and Time delay (0 – 10s)
  • Local (and optional remote) Test/Reset buttons
  • Isolated Auxiliary supply
  • 1 x SPDT/1 x SPNO Relay outputs
  • 44mm wide, DIN Rail mount

This product is used in conjunction with an external Core Balance Current Transformer (CBCT) and will detect residual sinusoidal alternating and pulsating direct currents. An adjustable trip level and time delay allows the product to be set according to the type of installation to be protected. When the level of leakage current being monitored exceeds the set trip level, the unit will trip. Typically, the product is used in conjunction with an external switching device (i.e. contactor, shunt trip). An auxiliary supply is required to power this product.

  • Monitoring function: Earth leakage
  • Trip level: 0.03 – 30A
  • Time delay: 0 – 10s
  • Output: 1 x SPDT 8A (S.O.) / 1 x SPNO 6A (P.S.O.) @ 250V (AC1)
  • Dimensions (mm): W:44 x H:85 x D:63.5

Aux. supply voltage options*:
12-125VDC (Order Code: 99-1014)
115/230VAC (Order Code: 99-1007)
400VAC (Order Code: 99-1015)

The 24VAC option is no longer available. Please refer to the multi-voltage ELR30PN.

* To be specified when ordering

Please note that this product requires an external toroid (CBCT) that should be also specified when ordering. Click here to view toroid options.

Distributors Stock Code Link
RS Components 5119121 (115/230VAC) Go to product
RS Components 1883546 (12-125VDC) Go to product
Farnell 1853734 (115/230VAC) Go to product
Farnell 4825112 (12-125VDC) Go to product

Typical applications include:

  • LV switchboards
  • Industrial control panels
  • Building services distribution
  • Plant room electrical panels

Key benefits:

  • Helps detect earth leakage — Type A residual-current monitoring can operate the relay output when leakage exceeds the 0.03 – 30A trip threshold.
  • Enables a control response — The relay output can be used with an appropriately specified contactor or shunt-trip device when a fault is detected.
  • Supports commissioning checks — Local and optional remote Test/Reset functions support commissioning and fault response.
  • Allows coordinated settings — The adjustable 0.03 – 30A trip and 0 – 10s delay allow selection to suit the protected installation.

Alternative product:

Icon: switch product
ELRP48V-30 Type A Earth Leakage Relay
  • Type A – Earth Leakage Relay
  • Selectable Trip level (0.03 – 30A) and Time delay (0 – 10s)
  • Local (and optional remote) Test/Reset buttons
  • Isolated Auxiliary supply
  • 1 x SPDT/1 x SPNO Relay outputs
  • 48 x 48mm, Panel mount
View