LELRF-0100

  • Type A – Earth Leakage Relay
  • Compact dimensions – 17.5mm wide (DIN Rail mount)
  • True RMS
  • Fixed Trip level (100mA) and Time delay (0s)
  • Combined Test and Reset button
  • 1 x SPDT Relay output

This product is used in conjunction with an external Core Balance Current Transformer (CBCT) and will detect residual sinusoidal alternating and pulsating direct currents. It is offered with a fixed trip level and instantaneous tripping. Typically, the product is used in conjunction with an external switching device (i.e. contactor, shunt trip). The relay is normally de-energised and energises on trip.
An auxiliary supply is required to power the product.

  • Monitoring function: Earth leakage
  • Trip level: 100mA
  • Time delay: 0s (instantaneous)
  • Aux. supply voltage: 230VAC (Order Code: 99-1211)
  • Output: 1 x SPDT 7A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Please note that this product requires an external toroid (CBCT) that should be also specified when ordering. Click here to view toroid options. Recommended sizes based on 100mA trip sensitivity are: 35mm, 50mm, 70mm and 120mm.

Alternative product:

Icon: switch product
ELRM44F-0100
  • Type A – Earth Leakage Relay
  • Fixed Trip level (100mA) and Time delay (0s)
  • Local (and optional remote) Test/Reset buttons
  • Isolated Auxiliary supply
  • 1 x SPDT Relay output
  • 44mm wide, DIN Rail mount
View