LXCVR

  • Under and Over voltage monitoring (Window)
  • Monitors own supply
  • Adjustable Trip levels
  • Adjustable Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

When power is applied, the output relay will energise provided the monitored supply voltage is above the set Under voltage trip level and below the set Over voltage trip level.

Under voltage:
If the voltage decreases below the set Under voltage trip level, the relay will de-energise. The voltage must increase above the trip level plus the set hysteresis setting before the relay will re-energise.

Over voltage:
If the voltage increases above the set Over voltage trip level, the relay will de-energise. The voltage must decrease below the trip level minus the set hysteresis setting before the relay will re-energise.

  • Monitoring function: Under/Over voltage
  • Trip level: Under: 75 – 95%/Over: 105 – 125%
  • Hysteresis: ≈2%
  • Time delay: 0.2 – 10s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Monitored supply voltage options*:
115V AC (Order Code: 99-3006)
230V AC (Order Code: 99-3007)

* To be specified when ordering

Distributors Stock Code Link
RS Components 8505395 (230VAC) Go to product
RS Components 8505398 (115VAC) Go to product
Farnell 2520636 (230VAC) Go to product
Farnell 2677809 (115VAC) Go to product



Alternative product:

Icon: switch product
LCVR/2
  • Under and Over voltage monitoring
  • Monitors own supply
  • Selectable nominal voltages
  • Adjustable Trip levels
  • Adjustable Time delay
  • 2 x SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed
View