SPD44

  • Surge protection
  • Incorporates transient voltage suppressors and gas discharge tubes
  • Suited to single phase supplies
  • 44mm wide, DIN Rail mount
  • Replaces M3SPD

The product is typically wired in parallel with the equipment/load and will protect against transient overvoltage’s/surges by allowing the surge current to pass through the device rather than the equipment.

  • Supply voltage: 230/240VAC/DC (Order Code: 99-3650)
  • Current rating: 16A (when used with suitable MCB)
  • Max. clamping voltage: < 900V (Phase/neutral) /
    < 1300V (Phase/earth)
  • Transient withstand capacity: (8/20us waveform) x5 @ 5kA (Phase/neutral) / x3 @ 5kA (Phase/earth)
  • Dimensions(mm): W:44 x H:85 x D:63.5