ELRM44V-30/2 (0.5s)

  • Type A – Earth Leakage Relay
  • Both internal relays configured to energise on trip
  • Selectable Trip level (0.03 – 30A) and Time delay (0 – 0.5s)
  • Local (and optional remote) Test/Reset buttons
  • Isolated Auxiliary supply
  • 1 x SPDT/1 x SPNO Relay outputs
  • 44mm wide, DIN Rail mount

This product is used in conjunction with an external Core Balance Current Transformer (CBCT) and will detect residual sinusoidal alternating and pulsating direct currents. Both internal relays are configured to energise on trip on this particular product.

An adjustable trip level and time delay allows the product to be set according to the type of installation to be protected. When the level of leakage current being monitored exceeds the set trip level, the unit will trip. Typically, the product is used in conjunction with an external switching device (i.e. shunt trip) and is typically controlled by the main relay output (RLY1). There is the option to utilise the second relay output (RLY2) which can be used to operate a panel lamp for example for visual indication purposes. An auxiliary supply is required to power this product.

  • Monitoring function: Earth leakage
  • Trip level: 0.03 – 30A
  • Time delay: 0 – 0.5s
  • Output: 1 x SPDT 8A (RLY1) / 1 x SPNO 6A (RLY2.) @ 250V (AC1)
  • Dimensions(mm): W:44 x H:85 x D:63.5

Aux. supply voltage options*:
12-125VDC (Please consult Sales)
24VAC (Please consult Sales)
115/230VAC (Order Code: 99-1053)
400VAC (Please consult Sales)

* To be specified when ordering

Please note that this product requires an external toroid (CBCT) that should be also specified when ordering. Click here to view toroid options.

Alternative product:

Icon: switch product
ELRM44V-30
  • Type A – Earth Leakage Relay
  • Selectable Trip level (0.03 – 30A) and Time delay (0 – 10s)
  • Local (and optional remote) Test/Reset buttons
  • Isolated Auxiliary supply
  • 1 x SPDT/1 x SPNO Relay outputs
  • 44mm wide, DIN Rail mount
View