LBVR/A

  • Under voltage monitoring of generator battery 
  • Monitors own supply
  • Adjustable Trip level
  • Adjustable Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

When power is applied, the output relay will energise if the monitored voltage is above the set trip level. When the voltage decreases below the set trip level the relay will de-energise after the set time delay period. The voltage must then increase above the trip level and plus the hysteresis setting before it will energise again.

  • Monitoring function: Under voltage
  • Supply voltage: 12 – 24V DC (Order Code: 99-3001)
  • Trip level: 9 – 28V DC
  • Hysteresis: 5% (fixed)
  • Time delay: 1 – 30s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions (mm): W:17.5 x H:89 x D:66.5mm
Distributors Stock Code Link
RS Components 8505411 Go to product
Farnell 2522315 Go to product

Alternative product:

Icon: switch product
LMCVR-20V
  • Under or Over voltage monitoring (selectable)
  • 5 Selectable voltage ranges (1V, 2V, 5V, 10V or 20V)
  • Adjustable Trip level, Hysteresis and Time delay + Latch
  • Isolated Auxiliary supply
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed
View