LXPRC/S/F

  • Under and Over voltage monitoring (Window)
  • Monitors own three phase, 3-wire supply
  • Detects incorrect phase sequence and phase loss
  • Fixed Trip levels/adj. Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present, the phase sequence correct and the phase to phase voltages within the fixed Under/Over trip levels. If any of these conditions are not met, the relay will de-energise.

  • Monitoring function: Under/Over voltage
  • Monitored supply voltage: 415VAC (Order Code: 99-4024)
  • Trip level (fixed): Under: 360V/Over: 457V
  • Hysteresis: ≈2%
  • Time delay: 0.2 – 10s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5