LXPRC/S/RD

  • Under/Over voltage monitoring (Window) with restart delay
  • Selectable Nominal voltages
  • Detects incorrect phase sequence and phase loss
  • Fixed Trip levels and adjustable Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present, the phase sequence correct and the phase to phase voltages within the fixed Under/Over trip levels. If any of these conditions are not met, the relay will de-energise.

  • Monitoring function: Under/Over voltage
  • Trip level (fixed): Under: 90% /Over: 110%
  • Hysteresis: ≈2%
  • Time delay: 4s
  • Restart delay: 1 – 500s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Monitored supply voltage options*:
200V/208V/220V/230V/240VAC (Order Code: 99-4006)
380V/400V/415V/440V/460VAC (Order Code: 99-4007)
* To be specified when ordering